超大型冷却塔施工全过程风荷载频域特性分析
作者:
作者单位:

1.南京航空航天大学民航学院南京211106;2.中国能源建设集团广东省电力设计研究院有限公司广州510700

作者简介:

通讯作者:

柯世堂,男,教授,博士生导师,E-mail:keshitang@163.com。

中图分类号:

TU279.7

基金项目:

国家自然科学基金NSFC-RGC合作研究 5171101042┫资助项目;国家自然科学基金面上 51878351┫资助项目;国家“九七三”计划 2014CB046200┫资助项目;江苏省优秀青年基金 BK20160083┫资助项目;江苏省“六大人才”高峰高层次人才计划 JZ-026┫资助项目国家自然科学基金NSFC-RGC合作研究(5171101042)资助项目;国家自然科学基金面上(51878351)资助项目;国家“九七三”计划(2014CB046200)资助项目;江苏省优秀青年基金(BK20160083)资助项目;江苏省“六大人才”高峰高层次人才计划(JZ-026)资助项目。


Frequency Domain Characteristics Analysis for Wind Loads During Construction of Super Large Cooling Tower
Author:
Affiliation:

1.College of Civil Aviation, Nanjing University of Aeronautics & Astronautics,Nanjing,211106,China;2.China Energy Engineering Group Guangdong Electric Power Design Institute Co., LTD.,Guangzhou,510700,China

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    以国内在建世界最高220 m超大型冷却塔为对象,基于大涡模拟(Large eddy simulation,LES)方法获得施工全过程冷却塔周围流场和风荷载时程,并将成塔风压分布结果与规范及实测曲线进行对比验证了数值模拟的有效性。在此基础上,对比分析了施工全过程塔筒平均与脉动风压根方差分布特性,系统对比研究了施工全过程风荷载频域特性,主要包括:典型测点风压功率谱特性、升/阻力系数功率谱、典型测点间环向相干性和升/阻力系数竖向相干性,并基于最小二乘法拟合给出随高度变化的典型测点功率谱计算公式。研究表明,施工期与成塔的脉动风荷载能量均集中在低频区,其中塔筒中部脉动风荷载在低频区能量较其他位置弱,随着施工高度的增加:脉动风荷载和层阻力系数功率谱密度函数均呈先减小后增大的趋势,升力系数功率谱在塔筒中下部谱值较大而上部较小,测点脉动风荷载环向相干性以及升/阻力系数竖向相干性均逐渐减弱。主要结论可供此类大型冷却塔施工期设计风荷载取值参考。

    Abstract:

    Taking the world’s highest 220 m domestic super large cooling tower under construction as the example, the flow field information and the three-dimensional aerodynamic forces during construction period are obtained based on large eddy simulation (LES). The average wind pressure distribution of the entire tower results are compared with the standard and the measured curves to verify the validity of the numerical simulation. On this basis, the average wind pressure and pulsating wind load variance distribution characteristics of the whole construction process of tower drum are contrasted and analyzed. Then the ritual law carrier frequency domain features of the whole construction process are systematically contrasted and studied, which include wind pressure power spectrum features of typical measurement points, the power spectrum of lift and resistance coefficient, ring to the coherence of typical measurement points, and the vertical coherence of lift and resistance coefficient. Finally, the calculation formula of the power spectrum with height for typical measurement points is fitted based on least square method. Studies show that the pulsating wind load energy of the tower under construction and the whole tower are both concentrated in the low frequency area, and the pulsating wind load at the central tower drum is weaker than that in other positions. With the increase of construction height, the power spectrum density function of pulsating wind load and layer resistance shows a trend of decreasing first and then increasing, the power spectrum value of lift coefficient is bigger in the lower part of tower and smaller in the upper part, and the ring to the coherence of typical measurement points and the vertical coherence of lift and resistance coefficient are gradually weakening. Main conclusions can provide a reference for the value designing of the wind load for this kind of large cooling tower during construction.

    参考文献
    相似文献
    引证文献
引用本文

徐璐,柯世堂.超大型冷却塔施工全过程风荷载频域特性分析[J].南京航空航天大学学报,2020,52(1):150-160

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2018-01-18
  • 最后修改日期:2018-09-27
  • 录用日期:
  • 在线发布日期: 2020-02-05
  • 出版日期:
文章二维码
您是第位访问者
网站版权 © 南京航空航天大学学报
技术支持:北京勤云科技发展有限公司